TEAT immersion temperature transmitter
Produal TEAT
Temperature transmitter/controller for water and ventilation ducts. For domestic hot water (DHW) measurement, the ATM, AT, or ATH sheath is required.
TEAT temperature transmitters are designed to measure cooling and heating water temperatures in automated HVAC systems.
These transmitters can also be used to measure air temperature in ventilation ducts, for example. They can be configured to create a P/PI control loop for local control at 0–10 V or 4–20 mA.
Temperature
°C
Modbus (Models -M)
0...50 °C, 0...100 °C, -50...50 °C, -50...150 °C
Yes (Models -LU, -LL, -M) with ML SER tool
±0,5 °C
PT 1000, PT100, NTC1.8, NTC2.2, NTC10, NTC10-AN, NTC10C, NTC10-KB, NTC20, Ni1000, Ni1000-LG, KP10, T1
Yes, with ML SER tool
Resistance, 0...10 V, 4...20 mA
24 Vac/dc, < 1 VA (Models -LU, -M); 15…35 Vdc (Model -LL)
IP54
Rear sheath and stuffing box at the bottom
0...60 °C
Water applications: with Produal protective cap (R½”) Air applications: with MT4270 flange
Probe Ø 6 x 85 mm
PBT, PC, PA, stainless steel
Optional display on transmitters (Models -LL, -LU, -M)
Sensor Pt1000
Sensor Pt100
Sensor NTC 1.8 (TAC / Schneider)
Sensor NTC 2.2 (Johnson)
Sensor NTC 10 (Trend / Distech)
Sensor NTC 10-AN (Schneider / Andover)
Sensor NTC 10-C (Carel)
Sensor NTC 10-KB (Satchwell)
Sensor NTC 20 (Honeywell)
Sensor Ni 1000
Sensor Ni 1000-LG (Siemens)
2-wire transmitter/controller, 15...35 Vdc power supply, 4...20 mA output
3-wire transmitter/controller, 24 Vac/DC power supply, 0...10 V < 2 mA output
Modbus transmitter/controller, 24 Vac/DC power supply, 0...10 V < 2 mA output