Pressure switch PS
Produal PS
Differential pressure switch with ranges from 20...200 Pa to 500...4500 Pa.
PS differential pressure switches are designed for monitoring overpressure, underpressure, or pressure differentials in systems handling air and other non-aggressive gases. These mechanical switches provide a cost-effective solution for monitoring the pressure of filters, fans, blowers, ventilation ducts, and ventilation heat recovery systems. Their switching point can be manually adjusted.
Differential pressure
Relay output: 250 Vac, 0.1 A, res.
Switching accuracy: max. ±15%
50 kPa
IP54
-20...60 ºC
0...95 %rH
90 x 105 x 63 mm
Range 20...200 Pa. ±8 Pa at the lower limit, ±15% at the upper limit. Switching difference: 20 Pa.
Range 30–300 Pa. ±8 Pa lower limit, ±15% upper limit. Switching difference: 25 Pa
Range 30–500 Pa. ±8 Pa lower limit, ±15% upper limit. Switching difference: 25 Pa
Range 40...600 Pa. ±8 Pa at the lower limit, ±15% at the upper limit. Switching difference: 35 Pa.
Range 100...1500 Pa. ±20 Pa at the lower limit, ±15% at the upper limit. Switching difference: 80 Pa.
Range 500...4500 Pa. ±100 Pa at the lower limit, ±15% at the upper limit. Switching difference: 250 Pa.