Immersion temperature sensor TEAT
Produal TEAT
TEAT sensors are designed to measure temperature in cooling and heating water pipes.
TEAT sensors are designed to measure temperature in cooling and heating water pipes.
TEAT temperature sensors are designed to measure cooling and heating water temperatures in automated HVAC systems. The sensors can also be used to measure air temperature in ventilation ducts, for example.
Temperatura
ºC
-50...120 °C
±0,2 a 0,5 °C
Resistance
0...60 °C
IP54
Rear sheath and stuffing box at the bottom
PBT, PC, PA, stainless steel
Sonda Ø 6 x 85 mm
Water applications: with Produal protective head (R½”), air applications: with MT4270 flange
100 Ω (0 °C), accuracy ±0.3 °C (0 °C), EN 60751/B
1000 Ω (0 °C), accuracy ±0.3 °C (0 °C), (Honeywell, Danfoss equivalent)
10 kΩ (25 °C), accuracy ±0.2 °C (25 °C) (Trend, Distech equivalent)
20 kΩ (25 °C), accuracy ±0.2 °C (25 °C) (Honeywell equivalent)
1000 Ω (0 °C), accuracy ±0.4 °C (0 °C), (Sauter equivalent)
1000 Ω (0 °C), accuracy ±0.4 °C (0 °C), (Siemens equivalent)
5025 Ω (25 °C), accuracy ±0.5 °C (25 °C)
1800 Ω (25 °C), accuracy ±0.3 °C (25 °C), (TAC, Schneider equivalent)
10 kΩ (25 °C), accuracy ±0.25 °C (25 °C) (equivalent to Schneider, Andover)
LM235Z, 10 mV/K, 2,98 V / 25 °C
10 kΩ (25 °C), accuracy ±0.25 °C (25 °C) (Carel equivalent)
2226 Ω (0 °C), accuracy ±0.4 °C (0 °C)